User Manual of A90 Series Inverter
220
Function
code
Function
code name
Parameter description
Unit
Default
setting
Attribute
F12.14
Restoration
of
default
setting
0: No operation
1: restoration of factory defaults
(excluding the motor parameters,
inverter parameters, manufacturer
parameters, running and power-on
time record)
0
○
You can set this parameter to 1 to restore the default settings of all parameters, except
the motor parameters (F01 group), inverter parameters, manufacturer parameters, power-on
time (F12.15/16) and operating time (F12.17, 18).
★
This operation is irreversible. Please set it carefully.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F12.15
Cumulative
power-on time h
0 - 65535
h
0
×
F12.16
Cumulative
power-on time min
0 - 59
min
0
×
F12.15 and F12.16 are used together to check the cumulative power-on time of the
inverter from delivery to the current moment (you only need to power on the inverter). The
cumulative power-on time is accurate to one minute and nearly 65,536 hours (about 7.5
years) at most.
If F12.15=50 and F12.16=33, it means that the current inverter has been powered on
for 2 days, 2 hours and 33 minutes.
★
This parameter can be viewed only and cannot be changed or cleared.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F12.17
Cumulative
running time
0 - 65535
h
0
×
F12.18
Cumulative
running time (min)
0 - 59
min
0
×
F12.17 and F12.18 are used together to check the cumulative operating time of the
inverter from delivery to the current moment (the inverter should be in the running status).