User Manual of A90 Series Inverter
285
7019H to
71FFH
Reserved
Working
status
7200H
~
73FFH
7200H status
word 1
Bit7 to 0 running
status
00H
Parameter setting
01H
Slave running
02H
JOG running
03H
Self-learning running
04H
Slave stop
05H
JOG stop
06H
Fault status
07H
Factory self-inspection
08H - 0FFH
Reserved
Bit15 to 8 fault
information
00H
Normal
running
of
inverter
xxH
Inverter fault status, where
“xx” is the fault code
7201H status
word 2
Bit0 setting
direction
1
- setting is valid
0
+ setting is valid
Bit1 running
direction
1
Reverse
frequency
output
0
Forward
frequency
output
Bit3 to 2 running
mode
00
Speed control mode
01
Torque control mode
10
Reserved
11
Reserved
Bit4 parameter
protection
1
Valid
parameter
protection
0
Invalid
parameter
protection
Bit6 - 5
Reserved
Bit8 to 7 setting
mode
00
Keyboard control
01
Terminal control
10
Communication control
11
Reserved
Bit9
Reserved
Bit10 warning
0
No warning
1
Warning status (see 7230H
for details)
Bit15 - 10
Reserved
7202H
monitoring
fre/-
Bit0
Output frequency
Bit1
Input frequency
Bit2
Synchronization frequency