User Manual of A90 Series Inverter
141
24
Switching of RUN
command to
keyboard
The current command channel depends on the status of these
two terminals and setting of F00.02. The priority is as
follows: “24: switching of RUN command to keyboard” >
“25: switching of RUN command to communication” >
“F00.02: command source option”. Refer to the F00.02
description for details.
25
Switching of RUN
command to
communication
26
Frequency source
switching
This terminal is mainly used to switch the frequency sources
in conjunction with the function code F00.06. When
F00.06=3 to 5, this terminal will be valid. Refer to the
F00.06 description.
27
Clearing of regular
running time
The regular running function is defined by F16.05. This
terminal can be used to clear the running time (reset the
remaining time of regular running). Refer to the F16.05
description.
28
Speed
control/torque
control switching
These two terminals are used to change the current inverter
control mode in conjunction with F13: When #28 terminal is
valid, speed control and torque control can be switched; and
when #29 terminal is valid, only speed control is enabled.
See the F13.00 description.
29
Torque control
prohibition
30
Motor 1/Motor 2
switching
This terminal is used to determine the current valid motor in
conjunction with F00.28. If #30 terminal is valid, the motors
will be switched based on the F00.28 setting. See the F00.28
description.
31
Resetting of simple
PLC status (running
from the first
segment, with the
running time
cleared)
When this terminal is valid, the simple PLC module will
restart running from the first segment. To further understand
this function, you can view the simple PLC description of
the F08 group.
32
simple PLC time
pause (keep running
at current segment)
When this terminal is valid, the simple PLC module will
keep running at the current segment. When this terminal is
invalid, the simple PLC module will continue to run after
running at the current segment.
33
Reserved
34
counter input
(≤250Hz)
It is a pulse input terminal that has the counting function.
The input pulse frequency is limited to 250Hz or below, and
only one terminal can be set with this function. See the
description of the function codes F16.03 to F16.04.
35
high-speed count
input (≤100kHz,
only valid for X7)
It is a pulse input terminal that has the counting function.
The input pulse frequency is limited to 100kHz or below.
This is valid only for the terminal X7 (that is, only
F02.06=35 can be set). See the description of the function
codes F16.03 to F16.04.