User Manual of A90 Series Inverter
143
47
Immediate DC
braking
The inverter will immediately stop running and be subject to
DC braking at the current frequency. The braking current is
dependent on the DC braking current (F04.21) in stop.
48
Fastest deceleration
to stop
The inverter will stop running within the minimum
allowable acceleration and deceleration time.
49
Reserved
50
External stop
When this terminal is valid, the inverter will stop running
according to the set stop mode (F04.19) and
acceleration/deceleration time 4 (F15.07/F15.08).
51
Switching of main
frequency source to
digital frequency
setting
When the main frequency source A is involved in setting, the
multi-segment speed model is not enabled and this terminal
is valid, the main frequency source will be switched to the
corresponding setting. The functions 51 to 56 can work
independently, but subject to the priority. See the description
of the function code F00.04 Table 7-1.
52
Switching of main
frequency source to
AI1
53
Switching of main
frequency source to
AI2
55
Switching of main
frequency source to
high-frequency
pulse input
56
Switching of main
frequency source to
communication
setting
57
Inverter enabling
When the inverter meets the operating conditions and the
current function terminal is valid, the inverter is able to run.
Otherwise, it will not run even if other operating conditions
are met.
★
: Inverter enabling function: If no terminal is selected, this
function is valid by default; if one terminal is selected, the
status of the selected terminal will prevail; and if more than
one terminal is selected and any selected terminal is invalid,
this function will not be valid.
58-68 Reserved
69
Prohibition of
reversing
When this terminal is valid, its function is the same as that in
the case of F00.21=1.
70-78 Reserved
165
Switching of main
frequency to VP