User Manual of A90 Series Inverter
157
terminal will not output the active level.
This function code is subject to bit operation. For specific settings, refer to the
description of the function code F03.08.
Function
code
Function code name
Parameter description Unit
Default
setting
Attribute
F03.09
Y1 valid delay time
0.000-30.000
s
0.000
●
F03.10
Y1 invalid delay time
0.000-30.000
s
0.000
●
F03.13
R1 valid delay time
0.000-30.000
s
0.000
●
F03.14
R1 invalid delay time
0.000-30.000
s
0.000
●
Valid
delay
Function i
output
Level
output
Invalid
delay
Pulse output width
Single pulse
output
Valid
Invalid
Valid
Invalid
Valid
Invalid
Fig. 7-15 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal
When the status of the selected function changes, the corresponding output terminal
will make a response with delay based on the function code settings. At present, the
terminals Y1 and R1 support this function. Details under default conditions: When the
function changes from the invalid to valid status and is maintained with the valid delay, the
corresponding output terminal will output the active level. When the function changes from
the valid to invalid status and is maintained with the invalid delay, the corresponding output
terminal will output the inactive level.
★
If the function code is set to 0.000s, the delay will be invalid.
Function
code
Function code name
Parameter
description
Unit
Default
setting
Attribute
F03.17 Single pulse time of
0.001 - 30.000
s
0.250
●