User Manual of A90 Series Inverter
133
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F01.09
Stator resistance
of asynchronous
motor
1~60,000 (rated power of motor: ≤
75 kW)
0.1~6,000.0 (rated power of
motor: > 75kW)
mΩ
Depending
on the
motor type
○
F01.10
Rotor resistance
of asynchronous
motor
1~60,000 (rated power of motor: ≤
75 kW)
0.1~6,000.0 (rated power of
motor: > 75kW)
mΩ
Depending
on the
motor type
○
F01.11
Leakage
inductance of
asynchronous
motor
0.01 ~ 600.00 (rated power of
motor: ≤ 75 kW)
0.001~ 60.000 (rated power of
motor: > 75 kW)
mH
Depending
on the
motor type
○
F01.12
Mutual
inductance of
asynchronous
motor
0.1 ~ 6,000.0 (rated power of
motor: ≤ 75 kW)
0.01 ~ 600.00 (rated power of
motor: > 75 kW)
mH
Depending
on the
motor type
○
F01.13
No-load
excitation
current of
asynchronous
motor
0.01 ~ 600.00 (rated power of
motor: ≤ 75 kW)
0.1 ~ 6,000.0 (rated power of
motor: > 75 kW)
A
Depending
on the
motor type
○
The function codes F01.09 to F01.13 are the parameters of the asynchronous motor.
They are usually unavailable to users. Please get them through motor parameter
self-identification (F01.34).
When the motor parameters (F01.01 to F01.08) are modified, the values of F01.09 to
F01.13 of the inverter will change automatically. Pay attention to this during operation.
Before the motor parameter self-identification, be sure to set F01.00 to F01.08
correctly according to the actual situation.
The specific meanings of motor parameters are shown in Fig. 7-6: