User Manual of A90 Series Inverter
138
F02.00=1 and F02.04=1, once one of the terminals X1 or X5 is valid, the “RUN” function
of the inverter will be enabled.
Table 7-4 Function List of Multi-function Digital Input Terminals
Settings
Function
Description
0
No function
The function is not used or the fault terminal is set to “0: no
function” to avoid misoperation.
1
Running terminal
(RUN)
When the command source is set to terminal control
(F00.02=1), and the function terminal is valid, the inverter
will execute the corresponding RUN function according to
the set value of the terminal control mode option (F00.03).
(See the explanation of the function code F00.03 for details.)
2
Running direction
F/R
When the command source is set to terminal control
(F00.02=1), and the function terminal is valid, the inverter
will execute the corresponding F/R function according to the
set value of the terminal control mode option (F00.03). (See
the explanation of the function code F00.03 for details.)
3
Stop control of
three-line operation
When the command source is set to terminal control
(F00.02=1), the terminal control mode is set to three-line
control (F00.03=2/3) and the function terminal is valid, the
inverter will execute the stop command. (See the explanation
of the function code F00.03 for details.)
4
Forward jog (FJOG)
When the command source is set to terminal control
(F00.02=1), and the function terminal FJOG is valid, the
inverter will run forward; if the function terminal RJOG is
valid, the inverter will run reversely; and if the two function
terminals are valid at the same time, the inverter will
decelerate to stop.
★
: When reverse running is prohibited, the reverse jog will
be invalid.
5
Reverse jog (RJOG)
6
Terminal UP
If the function terminal UP is valid, the frequency offset will
be increase at the rate defined by F12.11; and if the function
terminal DOWN is valid, the frequency offset will decrease
at the rate defined by F12.11.
If the UP/DOWN offset clear terminal is valid, the frequency
offset will be cleared to 0.
Final set frequency of the frequency source A = set
frequency of the frequency source A + UP/DOWN offset.
★
: The UP/DOWN function is valid only when the main
frequency source A is involved in setting.
The offset frequency can be viewed via F18.15.
The function of the terminal UP/DOWN is the same as that
of the UP/DOWN on the keyboard.
7
Terminal DOWN
8
Clear UP/DOWN
offset