User Manual of A90 Series Inverter
158
Y1 output
F03.19
Single pulse time of
R1 output
0.001 - 30.000
s
0.250
●
When one function output terminal is in the single pulse output mode (see F03.05 for
details), the pulse width of the active level can be controlled by setting the single pulse
output time, in order to meet different process or control requirements.
Details are given in
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F03.21 Options
of
analog
output M1
see Table 7-7 Function
List of Multi-function
Analog Output Terminal
0
○
F03.22 Options
of
analog
output M2
2
○
M1 and M2 are two multi-function analog output terminals. Their functions can be
defined separately by setting the values of the function codes F03.21 to F03.22.
For example, if F03.21=0 is defined, the function of the M1 terminal is to output the
“operating frequency (absolute value)”. The current |operating frequency| is reflected by the
output voltage. If the operating frequency increases from 0.00Hz to 50.00Hz (assuming
F00.16=50.00), the voltage of the M1 output port will increase from 0.00V to 10.00V under
the default conditions, showing the same change trend. Specific options are described in
Table 7-7 Function List of Multi-function Analog Output Terminal
Settings
Function
Description
0
Operating frequency
(absolute value)
0.00Hz to Fmax, corresponding to the output 0.0% to
100.0%
1
Set
frequency
(absolute value)
0.00Hz to Fmax, corresponding to the output 0.0% to
100.0%
2
Output
torque
(absolute value)
0.0% to 200.0%, corresponding to the output 0.0% to
100.0%
3
Set torque (absolute
value)
0.0% to 200.0%, corresponding to the output 0.0% to
100.0%
4
Output current
0.0A to 2*Ie, corresponding to the output 0.0% to 100.0%
5
Output voltage
0.0V to 1.5*Ue, corresponding to the output 0.0% to