User Manual of A90 Series Inverter
229
to F14.34 correspond to F01.00 to F01.34, which are motor nameplate parameters, motor
parameters and encoder parameters; the function code F14.35 corresponds to F00.01, which
is used to select the motor drive mode; the function codes F14.36 to F14.76 correspond to
F06.00 to F06.40, which are vector control parameters; and the function code F14.77 is
used to select the acceleration/deceleration time of the motor 2. Only the parameters of
F14.72 are described below. For the rest of the parameters, refer to the relevant parameters
of the motor 1.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F14.77
Acceleration/decelerati
on time options of
motor 2
0: the same as motor 1
1: acceleration and
deceleration time 1
2: acceleration and
deceleration time 2
3: acceleration and
deceleration time 3
4: acceleration and
deceleration time 4
0
○
F14.77=0
: the acceleration/deceleration time of the motor 2 is the same as that of the
motor 1. For details, see the description of the function codes F15.03 to F15.09;
F14.77=1/2/3/4
: the acceleration/deceleration time of the motor 2 is fixed as the
acceleration/deceleration time 1/2/3/4, corresponding to the function codes F00.14,
F00.15/F15.03, F15.04/F15.05, F15.06/F15.07 and F15.08, respectively.
7.16
Auxiliary Function Parameter Group of F15 Group
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F15.00 Jog frequency
0.00
to
maximum
frequency F00.16
Hz
5.00
●
F15.01
Jog
acceleration
time
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
5.00
●
F15.02
Jog
deceleration
time
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
s
5.00
●