User Manual of A90 Series Inverter
36
A90-4T013B
6
750V
wire
A90-4T017B
A90-4T025B
M5
3.0~4.0
10
A90-4T032B
A90-4T038B
PB, +, -, R, S, T, U, V, W,
A90-4T045B
16
A90-4T060
R, S, T, +, -, U, V, W
M6
4.0~5.0
25
A90-4T075
25
A90-4T090
M8
9.0~10.0
35
A90-4T110
35
A90-4T150
M6
M10
4.0~5.0
17.0~22.0
60
A90-4T176
R, S, T, P, +, -, U, V, W
60
A90-4T210
90
A90-4T253
R, S, T, P, +, -,
, U, V, W
90
A90-4T304
120
Note:
1: The specifications of the wire are dependent on its voltage drop. Under
normal circumstances, the voltage drop calculated by the following formula should be
less than 5V.
Voltage drop =
3
* wire resistivity (Ω/KM) * wire length (m) * rated current (A) *
10
-3
2: If the wire is in a plastic slot, it should be enlarged by one level.
3: The wire should be crimped to the round terminal suitable for the wire and terminal
screw.
4: The specification of the ground wire should be the same as that of the power cable
smaller than 16mm
2
. When the power cable is 16mm
2
or larger, the ground wire should
not be smaller than 1/2 of the power cable.