User Manual of A90 Series Inverter
115
ON, it indicates that the inverter is running. If this indicator is flickering, it indicates that
the inverter is in the status of deceleration to stop.
Regardless of the speed or torque reference input control, the inverter will run in the
input control mode at the jog speed once jogging is enabled.
F00.02=1: terminal control (LOC/REM indicator OFF)
The start and stop of the inverter are controlled by the start and stop control terminals
that are defined by the function codes F02.00 to F02.06. Detailed settings of terminal
control are dependent on F00.03.
F00.02=2: Communication control (LOC/REM indicator flickering)
The inverter start and stop are controlled by the host through the RS485
communication port. See the 7000H control description for details.
The final command source also depends on the input functions “24: switching
from the Run command to keyboard” and “25: switching from the Run
command to communication”. If the input function “24: switching from the
Run command to keyboard” is valid, the current command source is
“keyboard control”. If the input function “25: switching from the Run command to
communication” is valid, the current command source is “communication control”.
Otherwise, the command source depends on the setting of the function code F00.02.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.03
Options of
terminal
control mode
0: terminal RUN (running) and F/R
(forward/reverse)
1: terminal RUN (forward) and F/R
(reverse)
2: terminal RUN (forward), Xi (stop) and
F/R (reverse)
3: terminal RUN (running), Xi (stop) and
F/R (forward/reverse)
0
○
Terminal RUN:
Xi terminal is set to “1: terminal RUN”
Terminal F/R:
Xi terminal is set to “1: running direction F/R”
Terminal control can be divided into two types: two-line control and three-line
control.
Two-line control: