User Manual of A90 Series Inverter
106
and 2
F15.13
Acceleration and
deceleration time unit
0:0.01s
1:0.1s
2:1s
0
○
F15.14
Frequency hopping
point 1
0.00-600.00
Hz
600.00
●
F15.15 Hopping range 1
0.00-20.00, 0.00 is invalid
Hz
0.00
●
F15.16
Frequency hopping
point 2
0.00-600.00
Hz
600.00
●
F15.17 Hopping range 2
0.00-20.00, 0.00 is invalid
Hz
0.00
●
F15.18
Frequency hopping
point 3
0.00-600.00
Hz
600.00
●
F15.19 Hopping range 3
0.00-20.00, 0.00 is invalid
Hz
0.00
●
F15.20
Detection width of
output frequency
arrival (FAR)
0.00 - 50.00
Hz
2.50
○
F15.21
Output frequency
detection FDT1
0.00 to maximum frequency
F00.16
Hz
30.00
○
F15.22 FDT1 hysteresis
-(Fmax-F15.21)~F15.21
Hz
2.00
○
F15.23
Output frequency
detection FDT2
0.00 to maximum frequency
F00.16
Hz
20.00
○
F15.24 FDT2 hysteresis
-(Fmax-F15.23)~F15.23
Hz
2.00
○
F15.25
Options of analog
level detection ADT
0:AI1
1: AI2
0
○
F15.26
Analog level
detection ADT1
0.00-100.00
%
20.00
●
F15.27 ADT1 hysteresis
0.00 to F15.26 (valid down in one
direction)
%
5.00
●
F15.28
Analog level
detection ADT2
0.00-100.00
%
50.00
●
F15.29 ADT2 hysteresis
0.00 to F15.28 (valid down in one
direction)
%
5.00
●
F15.30
Options of energy
consumption braking
function
0: Invalid
1: valid
0
○
F15.31
Energy consumption
braking voltage
110.0-140.0 (380V, 100.0 =
537V)
%
125.0
(671V)
○
F15.32 Braking rate
20-100 (100 means that duty ratio
is 1)
%
100
●
F15.33
Operating mode with
set frequency less
than lower frequency
limit
0: running at the lower frequency
limit
1: Shutdown
2: zero-speed running
0
○