User Manual of A90 Series Inverter
104
proportional gain
ACR-P2
F14.51
Torque current
integral time constant
ACR-T2
0.00-600.00
0.00: no integral
ms
10.00
●
F14.52 Position loop gain
0.000 - 40.000
1.000
●
F14.53
SVC zero-frequency
processing
0: braking
1: not processed
2: seal the tube
2
○
F14.54
SVC zero-frequency
braking current
50.0-400.0 (100.0 is the no-load
current of the motor)
%
100.0
○
F14.55
SVC low-frequency
excitation current
50.0-150.0 (100.0 is the no-load
current of the motor)
%
100.0
○
F14.56
Voltage feedforward
gain
0 - 100
%
0
●
F14.77
Acceleration/decelera
tion time options of
motor 2
0: the same as motor 1
1: acceleration and deceleration
time 1
2: acceleration and deceleration
time 2
3: acceleration and deceleration
time 3
4: acceleration and deceleration
time 4
0
○
F14.78
Maximum frequency
of motor 2
1.00~600.00
Hz
50.00
○
F14.79
Upper frequency limit
of motor 2
Lower limit frequency F00.19 to
maximum frequency F14.78
Hz
50.00
●
F14.80
V/F curve setting of
motor 2
0: straight line V/F
1: multi-point broken line V/F
0
○
F14.81
Multi-point VF
frequency F1 of
motor 2
0.00 - F14.83
Hz
0.50
●
F14.82
Multi-point VF
voltage V1 of motor 2
0.0~100.0 (100.0 = Rated voltage) %
1.0
●
F14.83
Multi-point VF
frequency F2 of
motor 2
F14.81 - F14.85
Hz
2.00
●
F14.84
Multi-point VF
voltage V2 of motor 2
0.0-100.0
%
4.0
●
F14.85
Multi-point VF
frequency F3 of
motor 2
F14.83 to rated frequency of
motor (reference frequency)
Hz
5.00
●