User Manual of A90 Series Inverter
254
Or, set F01.34=2 and press
RUN
. The inverter will start the rotary self-identification
of the motor.
For the synchronous motor:
Set F01.34=11 and press
RUN
. The inverter will start the static self-identification of
the motor.
Or, set F01.34=12 and press
RUN
. The inverter will start the rotary self-identification
of the motor.
It takes about two minutes to complete the self-identification of the motor. Then the
system will return to the initial power-on status.
During the self-identification, if you press the STOP/RESET key
STOP
RESET
, “E24”
(parameter identification abnormality) will be displayed; and if you press the
STOP/RESET key
STOP
RESET
, the system will return to the parameter setting status.
If the self-identification fails, “E24” (parameter identification abnormality) will be
displayed. If the STOP/RESET key is pressed
STOP
RESET
, the system will return to the
parameter setting status.