7 Drive Machine Data (SIMODRIVE Drive MD)
04.96
7.2.2 FDD MD (data description - SW 3)
Block frequency current setpoint filter 4
1219
Default value
Lower input limit
Upper input limit
Units
3 999.0
1
7 999.0
Hz
Active
at once
Input of block frequency for current setpoint filter 4 (band-stop). When block frequencies of
< 10 Hz are input, the filter is deactivated (proportional element with a gain of 1). The filter is
activated via machine data MD 1200 and MD 1201.
Note:
The maximum block frequency input value is limited by the sampling frequency of the control
(MD 1000) (parameterization error).
1
1
MD 1219 < –––––––––––
= –––––––––
2 x MD 1000
2 x T
sampl.
MD 1000 = T
sampl.
=
62.5
µ
s
125.0
µ
s
=> MD 1219 <
8000 Hz
4000 Hz
Bandwidth current setpoint filter 4
1220
Default value
Lower input limit
Upper input limit
Units
100
0
1 000
Hz
Active
at once
Input of 3dB bandwidth for current setpoint filter 4 (band-stop). The filter is activated in
machine data MD 1200 and MD 1201.
Note:
When 0 is entered for the bandwidth, the filter is parameterized as a proportional element with
a gain of 1.
Motor rated speed
1400
Default value
Lower input limit
Upper input limit
Units
1 500
0
6 000
rev/min
Active on
Power On
Input of motor rated speed as specified on the motor data sheet (non-Siemens motor) or
automatic parameterization using machine data "Motor code number" (MD 1102).
Maximum motor operational speed
1401
Default value
Lower input limit
Upper input limit
Units
1 500
0
7 200
rev/min
Active
at once
Machine data MD 1401 defines the maximum operational speed of the feed motor. It is used
as a reference value for the speed setpoint interface and for the machine data "Monitoring
speed motor" (MD 1405). Its default value is set by means of motor selection (MD 1102) to
the rated motor speed as specified on the motor data sheet.
7–62
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
SINUMERIK 840C (IA)
Summary of Contents for SIMODRIVE 611-D
Page 2: ......