09.95
7 Drive Machine Data (SIMODRIVE Drive MD)
7.3.2 Drive MD (data description)
Direct servo loop absolute track (SW 5 and higher)
1033
Default value
Lower input limit
Upper input limit
Units
0000
0000
FFFF
Hex
Active on
Power On
Bit 0
Lighting failed
Replace encoder
Bit 1
Signal amplitude too small
Replace encoder
Bit 2
Code connection defective
Replace encoder
Bit 3
Overvoltage
Switch on/off, replace encoder
Bit 4
Undervoltage
Switch on/off, replace encoder
Bit 5
Overcurrent
Switch on/off, replace encoder
Bit 6
Battery change necessary
Change battery
Bit 7
Reserved
-
Bit 8
Reserved
-
Bit 9
Reserved
-
Bit 10
Protocol cannot be cancelled
Switch on/off, replace encoder
Bit 11
SSI level detected on data line hardware
Check encoder type, replace
Bit 12
TIMEOUT on reading measured value
Repeat, replace hardware
Bit 13
CRC error
Replace hardware
Bit 14
Reserved
-
Bit 15
Encoder defective
Replace encoder
Frequency pulse-width modulation
1100
Default value
Lower input limit
Upper input limit
Units
4 000/3 200
2 000
8 000
Hz
Active on
Power On
The frequency of the sampling triangle in the PWM inverter is defined in this machine data.
The default depends on the motor type (FDD ˆ
= 4000, MSD ˆ
= 3200) and is configured by the
drive configuration at the time of start-up. The frequency values are set as an MMC function
(see attached table).
Value table:
Default value
f
PBM
in Hz
T
PBM
in
µ
s
–
2000
500.0*
–
2285.7....
437.5*
–
2666.6....
375.0*
MSD
3200
312.5*
FDD
4000
250.0*
–
5333.3....
187.5*
–
8000
125*
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
7–81
SINUMERIK 840C (IA)