04.96
7 Drive Machine Data (SIMODRIVE Drive MD)
7.2.2 FDD MD (data description - SW 3)
Bandwidth current setpoint filter 2
1214
Default value
Lower input limit
Upper input limit
Units
500
0
1 000
Hz
Active
at once
Input of 3dB bandwidth for current setpoint filter 2 (band-stop). The filter is activated in
machine data MD 1200 and MD 1201.
Note:
When 0 is entered for the bandwidth, the filter is parameterized as a proportional element with
a gain of 1.
Block frequency current setpoint filter 3
1216
Default value
Lower input limit
Upper input limit
Units
3 999.0
1
7 999.0
Hz
Active
at once
Input of block frequency for current setpoint filter 3 (band-stop). When block frequencies of <
10 Hz are input, the filter is deactivated (proportional element with a gain of 1). The filter is
activated via machine data MD 1200 and MD 1201.
Note:
The maximum block frequency input value is limited by the sampling frequency of the control
(MD 1000) (parameterization error).
1
1
MD 1216 < –––––––––––
= –––––––––
2 x MD 1000 2 x I
sampl.
MD 1000 = T
sampl.
=
62.5
µ
s
125.0
µ
s
=> MD 1216 <
8000 Hz
4000 Hz
Bandwidth current setpoint filter 3
1217
Default value
Lower input limit
Upper input limit
Units
100
0
1 000
Hz
Active
at once
Input of 3dB bandwidth for current setpoint filter 3 (band-stop). The filter is activated in
machine data MD 1200 and MD 1201.
Note:
When 0 is entered for the bandwidth, the filter is parameterized as a proportional element with
a gain of 1.
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50