07.97
7 Drive Machine Data (SIMODRIVE Drive MD)
7.3.2 Drive MD (data description)
Table: Possible current and speed controller cycle combinations
SIN 840C with 611D
controller ...
Current
controller cycle
MD 1000
Speed
controller cycle
MD 1001
Comments
Single-axis performance
125
µ
s
125
µ
s
Default value
Single-axis performance
62.5
µ
s
62,5
µ
s
Minimum
Single-axis performance
125
µ
s
250
µ
s
as from SW 6
Single-axis performance
125
µ
s
500
µ
s
as from SW 6
2-axis performance
125
µ
s
125
µ
s
Default value/minimum
2-axis performance
1 axis present
62.5
µ
s
62,5
µ
s
Minimum
2-axis standard
125
µ
s
125
µ
s
Default value/minimum
2-axis standard
1 axis present
125
µ
s
125
µ
s
Default value/minimum
Notes:
•
Intermediate values are not permitted (parameterization error).
•
Exceeding the computing time on the speed controller clock cycle level is not permissible
and will lead to tripping of the drive.
Monitoring cycle
1002
Default value
Lower input limit
Upper input limit
Units
100 000
4 000
100 000
µ
s
Active on
Power On
The interrupt clock cycle is used for high-priority monitoring purposes. Note: The input value
for the clock cycle must be a whole multiple of 4 ms (parameterization error). For the default
value, the monitoring cycle time is 100 ms.
m x 4000
µ
s
m = 1, 2, 3 ... 25
Note:
The interrupts level must not be exceeded. If it is, the drive shuts down.
Configuration STS
1003
Default value
Lower input limit
Upper input limit
Units
0330
0000
FFFF
Hex
Active on
Power On
Caution:
Do not modify this machine data, the default corresponds to the optimum configuration. (For
Siemens service only)
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
7–75
SINUMERIK 840C (IA)