EAAM057608EN
GC250 Technical Manual 61
7.4.6.4
S.04 CONTROLLER
Page S.04 displays the specific information of the controller: date/time, alpha-numeric
identification (ID Code) and firmware revision.
7.4.6.5
S.05 DIGITAL INPUTS
Page S.05
displays the status:
Of the digital inputs of the controller.
Analogue inputs used as digital (if they are not used as digital they are displayed with
hyphens).
Pressing and holding the digit ▼ it is possible to display the turning inputs in two different
ways:
STATO LOGICO
: the controller shows the logic level of the inputs (active or inactive)
used in the management of the operating sequence.
STATO FISICO
: Electrical level (active or inactive, or high or low) actually present on
the input; this can be the opposite in comparison to the corresponding logic state.
Displayed in negative.
7.4.6.6
S.06 DIGITAL OUTPUTS
Page S.06
displays the status of the digital outputs of the controller. Pressing and
holding the digit ▼
it is possible to display the turning inputs in two different ways:
LOGIC STATUS
: the controller shows the logic level of the outputs (active or inactive)
used in the management of the operating sequence.
STATO FISICO
: the controller displays the electric level (active or not active, high or
low) really present on the input; it can be opposite compared to the corresponding
logic status. Displayed in negative.
7.4.6.7
S.17 ANALOGUE INPUTS
Page S.07
displays the value of the analogue inputs of the controller
T.13
,
T.14
,
T.15
,
of their reference terminal
T.12
, of
T.09
(D+) and of the analogue input
T.16
. For each input
the measure in Volt is displayed, for terminals
T.13
,
T.14
,
T.15
the measure in ohm is also
displayed.
7.4.7
Electrical measures (M.xx)
This mode displays all the information on the measurements taken by the controller on the
electric lines. Y
ou can scroll through the various pages using ▲ e ▼ buttons.
7.4.7.1
M.01 SYSTEM
Page M.01 displays on a single line format the plant diagram, highlighting:
The mains
The symbol is only displayed with SSB plants
. The symbol of
the mains is fix if the mains is within the tolerance and flashing if the mains is missing
or out of tolerance (see par. 9.2). Under it, the medium value of the three Mains
unchained voltages and the Mains frequency measured by the device are shown.
INFORMATION!
If an external mains sensor is used (see par. 9.2.2) the symbol
flashes or is fix according to the status of the external sensor, while the below
measures are
always
those of the internal sensor of the device.