GC250 Technical Manual 35
▪
144: Low oil pressure from Can-Bus.
▪
158: High oil temperature from Can-Bus.
▪
159: Maximum oil temperature from Can-Bus.
▪
198: Cumulative of warnings from Can-Bus.
▪
199: Cumulative of the alarms (locks) from Can-Bus
DOF.4034 Fuel faults.
It is activated in case of faults in the fuel level, i.e.:
▪
025: Minimum fuel level (from contact).
▪
026: Minimum fuel level (from analogue sensor)
▪
027: Low fuel level (from contact).
▪
028: Low fuel level (from analogue sensor)
▪
029: High fuel level (from contact).
▪
030: High fuel level (from analogue sensor)
▪
160: Water in fuel from Can-Bus.
DOF.4035 Breakers faults.
It is activated in case of faults of the GCB and MCB breakers, i.e.:
▪
013: Mains circuit breaker not closed
▪
014: Genset circuit breaker not closed
▪
023: Mains circuit breaker not open
▪
024: Genset circuit breaker not open
5.6.4
AND/OR logics
The AND/OR logics are, basically, a list of boolean conditions (true/false, on/off, 1/0), which
can be configured by the operator (programming), which the controller evaluates and the result
of which can be assigned to a digital output (see par. 5.6.1). For using the AND/OR logics with
a digital output, use the DOF.0103 function.
INFORMATION!
: the configuration of the AND/OR logics cannot be carried out
directly from the controller display, but it has to be carried out by PC with the BoardPrg3
software.
It is necessary to decide whether the list of conditions has to be evaluated as AND (they have
to be all verified) or as OR (it is enough that at least one condition is verified).
It is not possible
to have mixed logics AND/OR (it is possible using the virtual digital inputs, see
afterwards).