EAAM057608EN
GC250 Technical Manual 33
Code
Description.
Notes
DOF.0000 Not used.
DOF.0103 AND/OR logics. X
The status of the output is the result of the combination of the
AND/OR logics. See par. 5.6.4
DOF.1001 Glow plugs preheating.
Command for glow plugs preheating for Diesel engines; see par.
9.5.2
DOF.1003 Fuel valve.
Command for the fuel interception solenoid; see par. 9.5.2
DOF.1005 Engine start command. Command for the starter motor; see par. 9.5.2
DOF.1006 Stop command.
Command for engine stop with arrest when energized; see par.
5.4.2and par. 9.5.2
DOF.1032 Fuel pump.
Fuel pump activation command.
DOF.1034 Fuel pump solenoid
valve.
Command to activate the fuel interception solenoid on the fuel pump
line; see par. 11.1
DOF.1035 Inhibit DPF regeneration. Command to inhibit the regeneration of the particulate filter; see par.
DOF.1036 Force DPF regeneration. Command to force the regeneration of the particulate filter; see par.
DOF.2001 MCB under voltage coil. See par. 9.6
DOF.2002 MCB opening coil.
See par. 9.6
DOF.2003 GCB opening coil.
See par. . 9.6
DOF.2004 MCB stable opening
command.
See par. 9.6
DOF.2031 GCB under voltage coil. See par. . 9.6
DOF.2032 GCB opening coil.
See par. 9.6
DOF.2033 Impulse closing
command for GCB
See par. . 9.6
DOF.2034 GCB stable closing
command.
See par. 9.6
DOF.3001 Off/Reset
It activates when the controller is in OFF/RESET mode.
DOF.3002 MAN
It activates when the controller is in MANUAL mode.
DOF.3003 Auto
It activates when the controller is in AUTOMATIC mode.
DOF.3004 Test
It activates when the controller is in TEST mode.
DOF.3005 Remote start.
It activates when the controller is in REMOTE START mode.
DOF.3011 Controller not in
OFF/RESET mode
It activates when the controller is in MAN or AUTO mode.
DOF.3012 One of the automatic
modes.
It is activated when the controller is in one of the automatic operation
modes that is AUTO, TEST or REMOTE START.
DOF.3032 Generator in tolerance
It is active when the mains parameters are within the “mains
presence” window
DOF.3033 Mains in tolerance
It is active when the mains parameters are in the “mains live” window.
DOF.3061 Engine running.
It is active when the generator parameters are in the normal operation
window
DOF.3121 Load thresholds
It is activated to report, depending on the configuration, a status of
high load or low load. See par. . 11.2
DOF.3151 Reset faults.
It is activated when the controller goes in RESET mode.
DOF.3152 Outside siren.
It is activated together with the internal siren.
DOF.3153 X X
It is activated in OFF/RESET mode by pressing the STOP key: it can
be used to turn on possible external led to the controller, and have
one only procedure to test the warning lights
DOF.4001 Warnings
It is activated in presence of warnings
DOF.4003 Deactivations
It is activated in presence of deactivations
DOF.4004 Alarms.
It is activated in presence of alarms
DOF.4005 Alarms, deactivations
and unloads.
It is activated in the presence of alarms, deactivations and unloads.
DOF.4031 Generator faults.
It is activated in the presence of faults of the generator, i.e.:
▪
001: Minimum generator voltage.