118 GC250 Technical Manual
EAAM057608EN
29 High fuel level (from contact)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
To disable:
P.2002=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is enabled only when one of the digital inputs of the controller is configured to acquire the
high fuel level contact of the float (feature DIF.4213 -
“High fuel level” in parameter P.2001 or
equivalent for the other inputs) and if a time other than zero has been set for said input
(parameter P.2002 or equivalent). Active if the configured input remains continuously active
for the associated time.
30 High fuel level (from analogue sensor)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.4009 (*) Function for input T.13 (FL)
Fuel level (VDO) / General
fuel level or equivalent parameter for the other inputs
P.0343
Threshold for high fuel level
P.0344
Delay for high fuel level
To disable:
P.0344=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is enabled only when the controller is configured to use the analogue fuel level sensor
(P.4009 suitably configured), or if said sensor is physically connected to the device terminal.
It activates if the level measure remains continuously above or equal to threshold P.0343 (in
percentage) for time P.0344.
31 High coolant temperature (from contact)
Icon:
Type:
Warning
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
P.0216
Time of engine protection mask
To disable:
P.2002=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external high coolant temperature contact (feature DIF.4231 -
“High coolant
temperature” in parameter P.2001 or equivalent for the other inputs) and if a time other than
zero has been set for said input (parameter P.2002 or equivalent). It is only enabled if the
controller has been started by the controller (if the command for the fuel solenoid is activated)
and is disabled in the engine start/stop phases. It activates if the input configured is
continuously “active” for the time configured, but only after the time P.0216 (oil mask) from
engine start has elapsed (this is to allow you to start the engine idle, to cool it off)