120 GC250 Technical Manual
EAAM057608EN
To disable:
P.0338=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the controller acquires the measure of the engine coolant
temperature. It can acquire it from its input (T.15, P.4025 suitably configured) or from CAN-
BUS (P.0700 other than zero). It is only enabled if the controller has been started by the
controller (if the command for the fuel solenoid is activated) and is disabled in the engine
start/stop phases. It activates if the temperature remains continuously above or equal to
threshold P.0337 for time P.0338, but only after the time P.0216 (oil mask) from engine start
has elapsed (this is to allow you to start the engine idle, to cool it off).
35 Maximum oil temperature (from analogue sensor)
Icon:
Type:
Alarm
Category:
Engine protection
Related parameters:
P.4025 Function for analogue input T.15 (CT)
or equivalent
parameter for other inputs
P.0216
Time for engine protection mask
P.0375
Threshold for maximum oil temperature (°C)
P.0376
Delay for maximum oil temperature
P.0700
Engine type
To disable:
P.0376=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the controller acquires the measure of the engine oil
temperature. It can acquire it from analogue input T.15 (P.4025) or from CAN-BUS (P.0700
other than zero). It is only enabled if the controller has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
activates if the measure is continuously higher than or equal to the threshold P.0375 for time
P.0376, but only after the time P.0216 (oil mask) since engine start has elapsed.
37 Starter battery voltage, low
Icon:
Type:
Warning
Category:
Battery protection
Related parameters:
P.0362
Threshold for low battery voltage (%)
P.0363
Delay for low battery voltage
To disable:
P.0363=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is always enabled except when the cranking motor is activated. It activates if the battery
voltage is continuously lower than the threshold P.0362 for time P.0363.
The threshold P.0362 is expressed as a percentage of the rated battery voltage which is not
configurable but is automatically selected by the controller between 12 e 24 Vdc. Selection is
made when the controller is powered and every time it is forced in
OFF_RESET
. If the
controller previously sensed a value lower than, or equal to, 17V, it considers to be powered
by a 12V battery, otherwise it will consider a 24 V rated voltage.
38 Starter battery voltage, high
Icon:
Type:
Warning