128 GC250 Technical Manual
EAAM057608EN
65 Low coolant temperature (from analogue sensor)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.4025
Function for analogue input 15
(CT)
or equivalent parameter
for the other inputs
P.0353
Threshold low cooling temperature (°C)
P.0354
Delay for low cooling temperature
P.0700
Engine type
To disable:
P.0354=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the controller acquires the measure of the engine coolant
temperature. It can acquire it from its input (T.15, P.4025 suitably configured) or from CAN-
BUS (P.0700 other than zero). It activates if the coolant temperature remains continuously
below threshold P.0353 for time P.0354 (even with engine shut down).
98 Maximum time without CAN-BUS data (engine)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.0700
Engine type
P.0709
Signalling for CAN-BUS failure
P.0711
Maximum time without messages from engine
To disable:
P.0711 =0 (no for MTU engine)
Enabled in:
MAN, AUTO, TEST, REMOTE START
It’s enabled only if CAN-BUS is configured (P.0700 other than zero). For MTU MDEC engines
(value from 140 to 147 in parameter P.0700), it is enabled as per specification when the
controller does not continuously receive the message NMT ALIVE PDU for the set time. For
the other types of engines, it is activated if the controller does not continuously receive
messages from the engine for time P.0711. With P.0709 the protection is configured as
warning, deactivation or interlock.
105 Battery charger failure from CAN-BUS
Icon:
Type:
Warning
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 11 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the battery-charger
alternator failure status over the CAN BUS.
118 Maximum speed from CAN-BUS
Icon: