GC250 Technical Manual 41
Bit 10. If this bit is “ON”, the controller checks that the GCB is closed, to activate
possible warnings/locks configured with the preceding bits.
Bit 11. If
this bit is “ON”, the controller activates a fault only if the fuel valve is activated.
Bit 13. If this bit is “ON”, to activate any warning/lock configured with the preceding
bits, the controller checks the status of any digital input configured with the function
“2705 - Disable the protections on the ANALOGUE measures”. The warnings/locks
will be activated if no digital input is configured as such, or if they are all OFF.
Bit 14. If this bit is “ON”, the fault entails the arrest of the fuel pump
You can set any combination of these bit.
The following table shows the list of functions that can be associated to the ANALOGUE inputs:
Function Denomination
Thresholds T.16 T.13
T.14
T.15
T.09
AIF.0000 Not used
X
X
AIF.0100 Used as digital input
X
X
AIF.1000 Oil pressure (VDO)
X
X
AIF.1001 Oil pressure (general)
X
X
X
X
AIF.1100 Oil temperature (VDO)
X
X
AIF.1101 Oil temperature (general)
X
X
X
X
AIF.1110 Coolant temperature (VDO)
X
X
AIF.1111 Coolant temperature (general)
X
X
X
X
AIF.1200 Oil level (VDO)
X
X
AIF.1201 Oil level (general)
X
X
X
X
AIF.1210 Coolant level (VDO)
X
X
AIF.1211 Coolant level (general)
X
X
X
X
AIF.1220 Fuel level (VDO)
X
X
AIF.1221 Fuel level (general)
X
X
X
X
AIF.1300 D+ Signal
X
X
AIF.1601 Air temperature in the intake pipe
X
X
X
X
AIF.1603 Exhaust gas temperature (left bank)
X
X
X
X
AIF.1605 Exhaust gas temperature (right bank)
X
X
X
X
AIF.1641 Turbo pressure
X
X
X
X
All odd functions AIF.XXXX require the use of program BoardPrg3 for the definition or the
upload of the sensor characteristic curve (see par. 5.7.3In fact, every digital input can have
an AND/OR logic associated, which determines its status.
Functions AIF.1000, AIF.1100, AIF.1110, AIF.1200, AIF.1200, AIF.1210, AIF.1220 use pre-
set conversion curves suitable for the VDO most common sensors instead.
Temperature sensor VDO (AIF.1100, AIF.1110)
0 °C
1800 Ohm
50 °C
195 Ohm
100 °C
38 Ohm
150 °C
10 Ohm
Pressure sensor VDO (AIF.1000)
0 bar
10 Ohm
10 bar
180 Ohm
VDO Level Sensors (AIF.1200, AIF.1210, AIF.1220)
0 %
180 Ohm
100 %
10 Ohm