EAAM057608EN
GC250 Technical Manual 111
breaker is closed. It is enabled if, under the conditions previously mentioned, the generator
frequency is continuously below the threshold P.0305 for the time P.0306.
04 Maximum generator frequency
Icon:
Type:
Alarm
Category:
Generator/Loads protection
Related parameters:
P.0105
Rated frequency
P.0307
Threshold for maximum frequency
P.0308
Delay for maximum frequency
To disable:
P.0308=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is only enabled if the controller has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
is enabled if, under the conditions previously mentioned, the generator frequency exceeds
continuously the threshold P.0307 for the time P.0308.
05 Belt break (alternator battery-charger failure)
Icon:
Type:
Configurable (Block/Deactivation/Warning)
Category:
Engine protection
Related parameters:
P.4041
Function for the analogue input (D+)
P
.
0230
Threshold for engine idle (D+)
P.0231
Threshold for engine started (D+)
P.0357
Action for belt break
P.0349
Delay belt break
To disable:
P.0349=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the controller is configured to use signal D+ (P.4041 =
AIF.1300 -
“Signal D+”) and if that signal is physically linked to connector JL. The protection is
enabled if the engine was started from the controller (if the command for fuel solenoid is
activated). It is activated if voltage on the D + signal remains below threshold P.0230
consecutively for P.0349 time.
06 Maximum current
Icon:
Type:
Configurable (Block/Deactivation)
Category:
Generator protection
Related parameters:
P.0101
Number of generator phases
P.0102
Generator rated power
P.0106
Generator rated power
P.0309
Threshold for maximum current
P.0310
Delay for maximum current
P.0323
Action for maximum current and short circuit
To disable:
P.0310=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
The controller realises a depending on time protection in current (which therefore intervenes
as quickly as the current is in overload). The used curve is named EXTREMELY INVERSE,
and implements an I
2
t. It is a generator protection as it limits the thermal accumulation of the