GC250 Technical Manual 47
DIF.4014 Alarm (after oil delay).
Yes
If the input is “active”, an alarm (block) is issued if the
time set by means P.0216 is elapsed from the engine
running detection. The message shown is the one set by
means of the related “text” parameter.
DIF.4021 Warning (if GCB
closed).
Yes
When the inp
ut is “active”, if a GBC command is active, a
warning is activated.
DIF.4023 Deactivation (if GCB is
closed).
Yes
When the input is “active”, if a GBC command is active, a
deactivation is commanded.
DIF.4024 Interlock (if GCB is
closed).
Yes
When the input is “active”, if a GBC command is active, a
interlock is activated.
DIF.4031 Warning (if FUEL is
enabled).
Yes
When the input is active, if the fuel solenoid valve control
(JH_03) is active, a warning is activated.
DIF.4033 Deactivation (if FUEL is
enabled).
Yes
When the input is active, if the fuel solenoid valve control
is active, a deactivation is commanded.
DIF.4034 Interlock (if FUEL is
enabled).
Yes
When the input is active, if the fuel solenoid valve control
(JH_03) is active, an interlock is activated.
DIF.4051 Warning (the fuel pump
is turned off)
Yes
If the input is “active”, a warning is issued: the message
shown is the one set by means the
related “text”
parameter. The controller blocks the fuel pump as long as
this input is “active”
DIF.4201 Emergency stop
Yes
DIF.4211 Minimum fuel level
Yes
If the input is “active”, an interlock with a fixed description
(language-dependant) is activated. This function can be
also used for the “Fuel pump management” (see par.
11.1In fact, every digital input can have an AND/OR logic
associated, which determines its status (see par. ).
DIF.4212 Low fuel level
Yes
If the input is “active”, a warning with a fixed description
(language-dependant) is activated. This function can be
also used for the “Fuel pump management” (see par.
11.1In fact, every digital input can have an AND/OR logic
associated, which determines its status (see par. ).
DIF.4213 High fuel level
Yes
If the input is “active”, a warning with a fixed description
(language-dependant) is activated. This function can be
also used for the “Fuel pump management” (see par.
11.1In fact, every digital input can have an AND/OR logic
associated, which determines its status (see par. ).
DIF.4221 Minimum oil pressure
Yes
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) interlock is activated.
DIF.4222 Low oil pressure
Yes
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.
DIF.4231 High coolant
temperature
Yes
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.
DIF.4232 Maximum coolant
temperature
Yes
When th
e input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.