EAAM057608EN
GC250 Technical Manual 113
This protection is only enabled if the controller has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases.
Type is configurable with parameter P.0323 (though it cannot be configured as warning).
07 Manual stop while in AUTO
Icon:
Type:
Alarm
Category:
General
Related parameters:
P.0495
Keyboard options
To disable:
P.0495=1
Enabled in:
AUTO, TEST, REMOTE START
This protection is always enabled for stop command through the serial ports and it can be
disabled for th
e “STOP” button by setting in parameter P.0495 the value 1.
It is activated when pressing the “
STOP
” button on the front panel or sending a stop command
via USB, while in
AUTO
,
TEST
or
REMOTE START
.
08 Operating conditions failure
Icon:
Type:
Alarm
Category:
General
Related parameters:
P.0217
Maximum time for full speed conditions
To disable:
P.0217=0
Enabled in:
AUTO, TEST, REMOTE START
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated). It is activated when the generator voltages and frequency
are not steady within tolerance range within time P.0217 from the engine running
acknowledgement (or from the end of
the engine’s idle cycle, if enabled).