34 GC250 Technical Manual
EAAM057608EN
▪
002: Maximum generator voltage.
▪
003: Minimum generator frequency.
▪
004: Maximum generator frequency.
▪
006: Maximum current.
▪
008: Standard operation conditions not met.
▪
016: Short circuit.
▪
052: Voltage unbalance.
▪
053: Current unbalance.
▪
055: Wrong phase sequence.
▪
056: Low generator voltage.
▪
058: Low generator frequency.
▪
059: High generator voltage.
▪
060: High generator frequency.
DOF.4032 Engine faults.
It is activated in the presence of faults of the engine, i.e.:
▪
005: Belt break ( generator battery-charger failure)
▪
021: Engine not stopped.
▪
022: Engine not started.
▪
031: High coolant temperature (from contact).
▪
032: High coolant temperature (from analogue sensor)
▪
033: Maximum coolant temperature (from contact).
▪
034: Maximum coolant temperature (from analogue sensor)
▪
035: High oil temperature (from analogue sensor).
▪
037: Start battery low voltage.
▪
038: Start battery high voltage.
▪
039: Service required.
▪
041: Minimum oil pressure (from contact).
▪
042: Minimum oil pressure (from analogue sensor).
▪
043: Low oil pressure (from contact).
▪
044: Low oil pressure (from analogue sensor)
▪
049: High power.
▪
054: High oil temperature (from analogue sensor)
▪
062: Fault in connection to the CAN bus.
▪
065: Low coolant temperature (from analogue sensor)
▪
098: Communication with engine interrupted.
▪
105: Belt from Can-Bus is broken.
▪
132: High temperature of the coolant from the Can-Bus.
▪
134: Maximum temperature of the coolant from the Can-Bus.
▪
135: Minimum level of the coolant from Can-Bus.
▪
136: Low level of the coolant from Can-Bus.
▪
137: Low battery voltage from Can-Bus.
▪
142: Minimum oil pressure from Can-Bus.