132 GC250 Technical Manual
EAAM057608EN
198 Warnings cumulative Yellow lamp from CAN-BUS
Icon:
Type:
Warning
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 14 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the active state of its yellow
lamp over the CAN BUS.
199 Alarms cumulative Red lamp from CAN-BUS
Icon:
Type:
Alarm
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 15 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the active state of its red
lamp over the CAN BUS. Using bit 13 of P.0704 it is possible to configure the protection as
warning or alarm.
11
11.1
The device applies full management of the fuel pump, for loading the storage tank into the
tank on the machine. The pump can be managed automatically or manually using the controls
on the front panel.
From page E.10 (only viewable if an output for the pump command is configured) it is possible
to select the pump command mode. To this purpose it is necessary to:
Press and hold button ▼: the icons that identifies the current mode will be shown in
negative.
Use the vertical scrolling buttons ▲ and ▼ to select the desired mode.
Confirm keeping button▼pressed or cancel the modification pressing and holding ▲.
INFORMATION!
: the fuel pump control mode is a normal parameter (P.0400) of
the controller, therefore it can be modified including from the programming windows.
The following modes are available: