80 GC250 Technical Manual
EAAM057608EN
127 (Escape). It is not possible to set extended ASCII characters (over 127) and
the control ones (from zero to 31).
Bits
:
Some parameters are managed in bit. Each bit at 1 enables a function and each
bit at 0 disables a function. Each bit is assigned a value. The parameter must be set
as the result of the sum of the values associated to the functions you require to enable.
8 bits can be used. The description of these parameters is shown in a table like the
one below:
Bit
Value
Description
0
1
Enable function 1
1
2
Enable function 2
2
4
Enable function 3
3
8
Enable function 4
4
16
Enable function 5
5
32
Enable function 6
6
64
Enable function 7
7
128
Enable function 8
If the operator wants to:
o
Disable all functions: you must set 0 in the related parameter.
o
Enable all functions: the value to set is given by the sum
1+2+4+8+16+32+64+128 = 255.
o
Enable, for example, functions 3, 4, 6 e 8: the value to set is given by the sum
4+8+32+128 = 172 (where 4 is the value associated to function 3, 8 to function
4, 32 to function 6 e 128 to function 8).
Attention: the value must be set with the hexadecimal noting:
o
255
→
FF
o
0
→
00
o
172
→
AC
8.2.3
Set up limits
The operator has not to worry about verifying that the set up value is acceptable for the
controller since it is not possible to set up not acceptable values.
This goes for individual parameters; however, it is possible to set two or more parameters in
incongruent or incompatible ways. It is up to the operator to prevent this from occurring.
8.3
To exit the programming, press button
STOP
n times to scroll back to the main menu, then
press it again to exit programming. On the following access to the programming the main menu
will be shown.
8.4
WARNING: This procedure permanently reloads all factory parameters according
to access rights.
Sometimes, it may be useful to reload parameters factory values. To do so, it is first of all
necessary to select O
OFF/RESET
mode, access programming, and then press and hold ▲ e
▼. Reload of factory values will be confirmed by a message on the display.
Factory values
are reloaded only for parameters for which you are granted access rights.