EAAM057608EN
GC250 Technical Manual 115
by the controller (if the command for the fuel solenoid is activated) and is disabled in the engine
start/stop phases. It activates when the current on at least one phase remains continuously
above the P.0311 threshold for time P.0312. Type is configurable with parameter P.0323
(though it cannot be configured as warning).
18 - Overspeed.
Icon:
Type:
Alarm
Category:
Engine protection
Related parameters:
P.0105
Rated frequency (Hz)
P.0331
Threshold of maximum speed from frequency (in %)
P.0332
Delay for maximum speed from frequency
To disable:
P.0332=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is only enabled if the controller has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
activates if the generator frequency exceeds threshold P.0331 continuously, for time P.0332.
INFORMATION!:
Parameter P.0331 is expressed in percentage with respect to P.0105.
21 Engine not stopped.
Icon:
Type:
Alarm
Category:
General
Related parameters:
P.0214 Duration of stopping cycle (s)
To disable:
P.0214=0
Enabled in:
AUTO, TEST, REMOTE START
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated). It activates if the engine does not stop within the time set in
P.0214 (since the stop command).
This interlock can be activated even if another one is already active.
22 Overcrank
Icon:
Type:
Alarm
Category:
Battery protection
Related parameters:
P.0211 Numbers of starting attempts
To disable:
-
Enabled in:
AUTO, TEST, REMOTE START
This protection is always enabled. It activates if the controller has performed P.0211
consecutive engine start attempts (auto start) without success (engine running).