116 GC250 Technical Manual
EAAM057608EN
23 Mains circuit breaker (MCB) not open
Icon:
Type:
Deactivation/Warning
Category:
General
Related parameters:
P.2001
Function of input T.16 or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
To disable:
P.2002=0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the MCB status (feature DIF.3002 -
“MCB breaker status” in parameter P.2001 or
equivalent for the other inputs) and if a time other than zero has been set for said input
(parameter P.2002). It activates only when MCB is commanded to open and the status
acquired is continuously “active” (closed) for the time set. In auto mode it activates after three
consecutive attempts. It can be:
Deactivation
:when the controller is in one of the AUTO modes and if the stable
command is used for MCB closing (feature DOF.2004 in one of the digital outputs).
Warning
: for all other events.
24 Genset circuit breaker (GCB) not open
Icon:
Type:
Block/Warning
Category:
General
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
To disable:
P.2002=0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the GCB status (feature DIF.3001 -
“GCB breaker status” in parameter P.2001 or
equivalent for the other inputs) and if a time other than zero has been set for said input
(parameter P.2002 or equivalent). It activates only when GCB is commanded to open and the
status acquired is continuously “active” (closed) for the time set. In auto mode it activates after
three consecutive attempts. It can be:
Block
: when the controller is in AUTO mode with engine running and only if the stable
command is used for GCB closing (function DOF.2034 in one of the digital outputs).
Warning
: for all other events.
25 Minimum fuel level (from contact)
Icon:
Type:
Alarm
Category:
General
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
To disable:
P.2002=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the minimum fuel level contact of the float (feature DIF.4211 -
“Minimum fuel level” in