130 GC250 Technical Manual
EAAM057608EN
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the minimum coolant level
state over the CAN BUS
136 Low coolant level from CAN BUS
Icon:
Type:
Warning
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 6 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the low coolant level state
over the CAN BUS.
137 Low battery voltage from CAN BUS
Icon:
Type:
Warning
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 9 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the low battery voltage
state over the CAN BUS.
142 Minimum oil pressure from CAN BUS
Icon:
Type:
Alarm
Category:
Engine protection
Related parameters:
P.0700
Engine type
P.0704
Anomalies deactivation mask from Can-Bus
To disable:
bit 1 of P.704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the minimum oil pressure
state over the CAN BUS.
144 Low oil pressure from CAN BUS
Icon:
Type:
Warning
Category:
Engine protection