EAAM057608EN
GC250 Technical Manual 121
Category:
Battery protection
Related parameters:
P.0364 Threshold for high battery (%)
P.0365
Delay for high battery voltage
To disable:
P.0365=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is always enabled, except when the starter motor command is activated. It
activates if the battery voltage is continuously above threshold P.0364 for time P.0365.
The threshold P.0364 is expressed as a percentage of the rated battery voltage which is not
configurable but is automatically selected by the controller between 12 e 24 Vdc. Selection is
made when the controller is powered and every time it is forced in
OFF_RESET
. If the
controller previously sensed a value lower than, or equal to, 17V, it considers to be powered
by a 12V battery, otherwise it will consider a 24V rated voltage.
39 Service required
Icon:
Type:
Configurable (Warning/Block/Deactivation)
Category:
General
Related parameters:
P.0424
Interval for service 1 (working hour)
P.0425
Type of action for service 1
To disable:
P.0424=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It activates after P.0424 engine running hours since parameter P.0424 was last set, by issuing
a warning, or triggering a deactivation or an interlock, based on the settings of the P.0425
parameter. It cannot be cancelled even disconnecting the controller's power supply. Only
possible setting P.0424 again, setting it to zero to disable the function or confirming the actual
value or setting a new one.
Engine operating hours are counted even when engine is not started by the controller.
To be programmed, parameters P.0424 and P.0425 req
uire “installer” access level: this
function can be used for genset rental in order to lock the genset when the established hours
are elapsed.
41 Minimum oil pressure (from contact)
Icon:
Type:
Alarm
Category:
Engine protection
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
P.0216
Time of engine protection mask
To disable:
P.2002=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external minimum oil pressure contact (feature DIF.4221 -
“Minimum oil pressure”
in parameter P.2001 or equivalent for the other inputs) and if a time other than zero has been
set for said input (parameter P.2002 or equivalent). It is only enabled if the controller has been
started by the controller (if the command for the fuel solenoid is activated) and is disabled in
the engine start/stop phases. It activates if the input configured is continuously “active” for the