EAAM057608EN
GC250 Technical Manual 71
The first line always shows the numerical indication of the selected function and the number
of functions in the menu. The following display lines are used in order to show the selectable
functions.
The selected voice is highlighted in negative (REVERSE).
Use the ▲ and▼ buttons to cyclically scroll through the menu to the lower and upper index
items (i.e. pressing the ▲ allows to directly cycle from the first item to the last one).
Keeping button ▼ pressed, the selected function activates (the one highlighted in negative);
keeping button ▲ pressed you return to page “H.03”.
7.4.9.2
Events pages (
)
Events: at the time when an event (previously configured) occurs, the board adds a record in
this archive. The capacity is of 64 records. If the archive is full and a new event occurs, the
less recent is overwritten (so always the last 64 events are stored). For each event are
recorded, in addition to the numeric code, also the date/time in which the event occurred, the
operation mode of the controller, the engine, the generator, the mains and the change-over in
that moment. If the event is an anomaly, measures described for the analogue archives are
also stored . The configuration of which event to be recorded is possible by means of
parameter
P.0441
with a bit management:
Bit
Value
P.0441
Ver.
Description
0
1
1.00 Controller mode.
1
2
1.00 Mains statuses.
2
4
1.00 Generator statuses.
3
8
1.00 Engine statuses.
4
16
1.00 MCB and MGCB statuses.
5
32
1.00 MCB and MGCB commands.
6
64
1.00 Start/stop requests.
7
128
1.00 Fuel pump controls.
The following table lists all possible event codes.
Code
Icon
Versio
n
Recording cause
EVT.1001
1.00
OFF_RESET
EVT.1002
1.00
MAN
EVT.1003
1.00
AUTO
EVT.1004
1.00
TEST
EVT.1005
1.00
REMOTE START
EVT.1010
1.00
Mains failure (flashing)
EVT.1011
1.00
Mains live (out of tolerance)
EVT.1012
1.00
Mains in tolerance
EVT.1013
1.00
Inhibition activated (from configurable input)
EVT.1014
1.00
Inhibition not activated (from configurable input)
EVT.1020
1.00
Generator failure
EVT.1021
1.00
Generator on
EVT.1022
1.00
Generator in tolerance
EVT.1030
1.00
GCB Close command