EAAM057608EN
GC250 Technical Manual 117
parameter P.2001 or equivalent for the other inputs) and if a time other than zero has been
set for said input (parameter P.2002 or equivalent). Active if the configured input remains
continuously active for the associated time.
26 Minimum fuel level (from analogue sensor)
Icon:
Type:
Alarm
Category:
General
Related parameters:
P.4009 (*) Function for input T.13 (FL)
Fuel level (VDO) / General
fuel level or equivalent parameter for the other inputs
P.0347
Threshold for minimum fuel level (%)
P.0348
Delay for minimum fuel level
To disable:
P.0348=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is enabled only when the controller is configured to use the analogue fuel level sensor
(P.4009 suitably configured), or if said sensor is physically connected to the device terminal.
It activates if the level measure remains continuously below or equal to threshold P.0347 (in
percentage) for time P.0348.
27 Low fuel level (from contact)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.2001 Function of input T.16
or equivalent for other inputs
P.2002
Delay for input T.16 or equivalent for other inputs
To disable:
P.2002=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is enabled only when one of the digital inputs of the controller is configured to acquire the
low fuel level contact of the float (feature DIF.4212 -
“Low fuel level” in parameter P.2001 or
equivalent for the other inputs) and if a time other than zero has been set for said input
(parameter P.2002 or equivalent). Active if the configured input remains continuously active
for the associated time.
28 Low fuel level (from analogue sensor)
Icon:
Type:
Warning
Category:
General
Related parameters:
P.4009 (*) Function for input T.13 (FL)
Fuel level (VDO) / General
fuel level or equivalent parameter for the other inputs
P.0345
Threshold for low fuel level (%)
P.0346
Delay for low fuel level
To disable:
P.0346=0
Enabled in:
MAN, AUTO, TEST, REMOTE START
It is enabled only when the controller is configured to use the analogue fuel level sensor
(P.4009 suitably configured), or if said sensor is physically connected to the device terminal.
It activates if the level measure remains continuously below or equal to threshold P.0345 (in
percentage) for time P.0346.