22 GC250 Technical Manual
EAAM057608EN
ANALOGUE INPUTS
T.09
AI_CONTROLLER_T09 (DP)
N.U.
D+ Voltage measurement
T.13
AI_CONTROLLER_T13 (FL)
N.U.
Fuel level sensor
T.14
AI_CONTROLLER_T14 (OP)
N.U.
Oil pressure sensor
T.15
AI_CONTROLLER_T15 (CT)
N.U.
COOLING TEMPERATURE sensor
T.16
AI_CONTROLLER_T16
DIGITAL INPUT T.16
Available
5.2
The device can manage two types of plants:
-
SSB
– Single Stand By
: it is the case of the emergency plant in which the electric mains
status is monitored; the genset is usually started automatically in case of anomalies on
the mains and it is stopped when anomalies stop.
-
SPM
– Single Prime Mover
: it is a plant where the mains is not present; the generator is
usually started manually or from remote to supply the loads.
The selection is done through parameter P.0802
P.0802 = 1 for SSB plants (default configuration)
P.0802 = 0 SPM plants.
According to the plant type, the principle connection diagram changes, as indicated in the
following paragraphs.