EAAM057608EN
GC250 Technical Manual 55
7.3
LED OFF
LED steady ON
LED flashing
Signalling
Function
Indicates that the operation mode is
OFF/RESET
Indicates that you are accessing the
PROGRAMMING
menu
The Gen-set control module is in another operating mode.
AUTO
Indicates that the operation mode is
AUTOMATIC
Flashing at 50% indicates that the operating mode is
TEST
Flashing at 90% indicates that the operating mode is
REMOTE
START
.
The Gen-set control module is in another operating mode.
MANUAL
Indicates that the operation mode is
MANUAL
Indicates that the operation mode is
MANUAL
and that the
protected start mode is active.
The Gen-set control module is in another operating mode.
ALARM
Indicates the presence of at least one lockout, one deactivation
or power-off
There is at least one active warning.
No anomalies.
ENGINE
RUNNING
Indicates engine running
Indicates engine idle