Wiring
3-27
CSD7 Servo Drive (EtherCAT)
Timing Chart
When a safe state is switched to an unsafe state as shown in the
figure below, the time T1 taken until EDM signal is turned off is
maximum 1 msec, and the time T2 taken until the torque is off is
maximum 0.5 ms.
* EDM (External Device Monitor) : It is used as a safe state output
signal.
SFI1
SFI2
EDM
Motor
Torque
Drive
Enable
T2
T1
T1
T1 : Max 1.0ms
T2 : Max 0.5ms
STO Wiring
Connecting to Safety Switch
Safety Sensor
Servo Amp
Contact Output
Safety
Input
Safety Input
EDM Output
24V
0V
SFI1+
SFI1-
SFI2+
SFI2-
EDM+
EDM-