Application
9-47
CSD7 Servo Drive (EtherCAT)
If the power failure lasts for a long time, normal motor control may be
not available.
Select one of the following settings so as to prevent ‘AC Line Loss Alarm
(E.037)' during the use of SAG function.
1.
Set AC Line Open-phase Detection to ‘Disable’ (0x2002[04] = Ft-
0.02[D3] = 1)
2.
If AC Line Open-phase Detection is set to ‘Enable’ (0x2002[04] = Ft-
0.02[D3] = 0), set 0x2504 (Ft-5.04, the delay time of momentary
power failure) longer than 0x250D (Ft-5.13, the torque limit value
duration of SAG function).
Note
AC Input
AC Err
SAG
Warning
Servo On
Fault
20 msec
SAG Tq Release Time
AC Loss Delay Time