Tuning by Gain Setting
8-41
CSD7 Servo Drive (EtherCAT)
Initial Torque Bias Setting
Set the initial torque bias to the following parameter.
0x240C
Initial Torque Bias
CSP
Setting Range
Size (Data Type)
Unit
Access
PDO Map
Attribute
Init Value
Ft-no
-100~100
4 byte(UDINT)
%
RW
-
Always
0
Ft-4.12
Ft-4.12
Initial Torque Bias
Description
The value of torque command is started from setting value of
this parameter.
You can prevent falling of load, because the torque command is
generated in the opposite direction of gravity when Servo-ON
signal is entered.
For another method of brake control, see the
“
You can prevent the instantaneous drop of load
just by setting the brake control timing.
Note
If you set the value of initial torque bias 0x240C
(Ft-4.12) too high, the load can temporarily goes
up.
Be careful to make appropriate setting value.