Page 78
The
fourth parameter
and the
fifth parameter
for each relay set the
Alarm
“
ON
” and “
OFF
” points. For a
high alarm
the “
ON
” is set
higher
than
“
OFF
”. For
low
alarm
then “
ON
” is set
lower than
“
OFF
”. See the
appropriate
alarm ID,
table (
P212, 222, 232, 242, 252
) for further
information.
When P211, 221, 231, 241, 251 = 1 (Level), 2 (Rate of Change) or 3
(Temperature)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.
P214, P224, P234, P244, P254 - Relay Setpoint 2
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.
Important Information
Setpoints
are entered in values according to the
function
selected.
Level -
entered in Measurement Units P104 or % of span as referenced
to Empty Level.
Rate of Change -
entered in Display Units per minute or % of span per
minute. For an alarm on a increasing level enter setpoints as a positive
value, for an alarm on a decreasing level enter setpoints as a negative
value.
Temperature -
entered in ºC.
See the appropriate
alarm function
, table (
P211, 221, 231, 241, 251
)
for further information.
*
To set figures in % press the
hot key to show and enter % figure
relative to empty level.
When P211, 221, 231, 241, 251 = 4 (Loss of Echo)
or
5 (Loss of Clock)
The
fourth
and
fifth
parameters
have no function and will not be
displayed.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...