Page 52
To program the
FlowCERT
LITE
for
Example 3 BS3680 Weir
by using the
Quick Setup
menu, proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997 and press
ENTER
Using the ‘right’ arrow key go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
Question
Option
PMD Type
3 = 3680 Weir
3680 Flumes
1 = Rectangular
Calculation
1 = Absolute
No. of Alarms
1 = 1 Alarm
Type Alarm 1
1 = High
Alarm No 1
3 = Set Relay 3
Xducer
1 = dB3
Volume Units
5 = US gallons
Time Units
2 = Per Minute
Measnt. Units
5 = inches
Empty Level
40.0 inches
Minimum Head
0.000 inches
Maximum Head
16.0 inches
Total Enable
1 = On
Totaliser ( R )
1 =Yes
Total Multiplier
7 = *1000
App. Width (Dim A)
18.0 inches
Crest Width (Dim B)
12.0 inches
Crest Height (Dim C)
10.0 inches
Programming is now complete and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the
FlowCERT
LITE
will return to
Run Mode
.
Note
If relay setpoints do not meet the exact requirements of the
application, they can be modified to suit by pressing ENTER when,
“For More Options Hit Enter”, is displayed, and entering new values
to relay setpoints as required. Alternatively the relevant relay
setpoint can be accessed either by the main menu system or directly
via parameter number and changed as necessary.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...