Page 12
Terminal Connections
Important Information
All terminal connection screws should be tightened to 4.5in.lbs.
(0.5Nm)
.
Care should be taken not to over tighten the screws.
Power
FlowCERT
LITE
can operate from mains AC and automatically from DC or
battery backup in the event of power failure, or can be operated permanently
from DC or batteries.
Important Information
The protective earth must be connected prior to any other cabling
taking place. This is connected to terminal 3, on all wall mount
units, and should be tightened to 4.5in.lbs. (0.5Nm).
The AC and DC wiring should be completed using either 16 – 14AWG
(1.5–2.5mm
2
) stranded or 16 – 14AWG (1.5–4mm
2
) solid wire.
An external supply isolator/circuit breaker (AC or DC) must be fitted near to
the unit and labelled to identify the instrument to which it refers.
Transducer
The transducer should be installed, and connected, in accordance with the
installation instructions contained in the Transducer User Guide.
The entire range of standard dB transducers is certified for use in hazardous
areas and different models are available for use in Zone 1 or Zone 0.
Wire the transducer to the
FlowCERT
LITE
’
s transducer terminals, terminal
numbers will depend on the unit type, as follows:
Transducer 1
Terminal Connection Details
Unit Type
Green
Screen
Red
Power
White
Signal
Black
0 volts
Wall Mount
37
38
39
40
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...