Control
When P210, 220, 230, 240, 250 = 3 (Control)
When a relay is being set up as a
control
relay, the
second parameter
that
will be displayed in the menu determines its
function.
P211, P221, P231, P241, P251, Relay Function,
This function allows the relay to be assigned to specific
control
functions
(other than pumps and alarms) several of these functions work in relation to
time.
This can be used to activate devices based on elapsed time or running
cycles, such as a timed rake control to keep a ram lubricated if idle for long
periods, or penstock/gate operation.
Options
Description
0 = Off
Relay is always de-energised
1 = Time
Relay will
energise
“
ON
” after the
Cycle time
that is
set in Relay
Setpoint 2
(P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4).
And turns “
OFF
”,
de-energises
, after the
On Time
Period
that is set in Relay
Setpoint 1
(P2
1
3, 2
2
3,
2
3
3, 2
4
3, 2
5
3)
2=Step Time
Step Time Control allows relays to be used to control
a device, such as a motorised valve or gate, in order to
maintain the level within two predetermined points.
Relays will
energise
“
ON
” when Step Time condition
is in effect and
de-energises
“
OFF
” when Step Time
goes off. One relay will be required to control an
increase in level, (‘open’ the device) and a second
relay is required to control a decrease in level, (‘close’
the device).
Alarm ID
(P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2) is
used to assign the relay to control either the
open
or
close
condition. Step Time Control relay requires
three setpoints. The first set point (P2
1
3, 2
2
3, 2
3
3,
2
4
3, 2
5
3) determines the
level
, at which the relay is to
be activated, (N.B. level setpoint for
open
relay,
increase
the level, must be
lower than
the setpoint
for the
close
relay,
decrease
the level). The relay will
energise
“
ON
” after the
Limit time
that is set in
Relay
Setpoint 3
(P2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
5
5). And
turns “
OFF
”,
de-energises
, after the
Drive Period
that is set in Relay
Setpoint 2
(P2
1
4, 2
2
4, 2
3
4, 2
4
4,
2
5
4).
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...