Page 102
Auxiliary
P810 Units
This parameter determines whether the
Measurement units
(
P104
) are
displayed on the auxiliary line of the display in run mode.
Option
Description
0 = No
Measurement units
will not
be displayed
1 = Yes (Default)
Measurement units
will
be displayed
P811 Alarms Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when an alarm relay is switched
on or off. The message is in the form “Alarm High ON”, where the ‘High’ is
determined by the setting of the relay
Alarm ID
(
P212, 222, 232, 242, 252
).
Option
Description
0 = No (Default)
Alarm messages
will not
be displayed
1 = Yes
Alarm messages
will
be displayed
P812 General Control or Pump Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a pump or general control
relay is switched on or off. The message is in the form “General 1 ON”,
where the number displayed is the number of the relay.
Option
Description
0 = No (Default)
Pump messages
will not
be displayed
1 = Yes
Pump messages
will
be displayed
P813 Control Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a control relay is switched
on or off. The message is in the form “Time ON”.
Option
Description
0 = No (Default)
Control messages
will not
be displayed
1 = Yes
Control messages
will
be displayed
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...