Page 88
Common Parameters
P216, P226, P236, P246, P256 - Relay Allocation
This parameter determines which input the relay will act on. In most cases,
this will not need to be changed from the default.
Option
Description
1= Xducer 1 (Default)
Relay acts on Xducer 1calculated levels.
P217, P227, P 237, P247, P257 - Relay Closures
The
FlowCERT
LITE
will record how many times each relay is operated,
this parameter displays the number of times the relay has activated since the
relay has been in use. It can be reset with any value.
P218, P228, P238, P248, P258 - Relay Fail Safe
Your
FlowCERT
LITE
has a general fail-safe parameter
P808
. However,
this can be overridden so that each individual relay has its own independent
fail safe mode.
This parameter determines what the relay will do in the event of the
Fail
safe
Time
(
P809
) expiring.
Option
Description
0 = Default
Relay assumes system default mode P808
1 = Hold
Relay remains in its current state
2 = De-Energise
Relay will De-Energise
3 = Energise
Relay will Energise