Page 36
For More Options Hit Enter
Parameter
Set Value
Description
P213 / P214
Relay 1
ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P223 / P224
Relay 2
ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P233 / P234
Relay 3
ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P243 / P244
Relay 4
ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P253 / P254
Relay 5
ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P708 Flow
Decimal
2
Set the number of decimal points required
in the flow rate display
P709 Flow
Cut Off
5.00%
Enter as a percentage of maximum flow,
the minimum flow rate to be added to the
totaliser.
P830
mA Out
Range
2= 4 to 20
mA
What the mA output uses for the range.
0= Off, 1= 0 to 20 mA, 2= 4 to 20 mA,
3= 20 to 0 mA, 4= 20 to 4 mA.
P870
Fill Damping
393.7
inches/min
Rate of maximum fill rate (set above the
actual fill rate of the vessel).
P871
Empty
Damping
393.7
inches/min
Rate of maximum empty rate (set above
the actual empty rate of the vessel).
The default values used for determining the
relay setpoints
, when setting
Alarm
relays, via the
Quick Setup
menu are entered as a % of span and are
as follows.
Relay Function
Alarm ID
On
Setpoint
Off
Setpoint
Alarm
Hi Hi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
Lo Lo
5%
10%
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...