To program the
FlowCERT
LITE
for
Example 1 V-Notch Weir
by using
the
Quick Setup
menu proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997 and press
ENTER
Using the ‘right’ arrow key go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and press
ENTER
.
Question
Option
PMD Type
1 = Exponent
Exponent
6 = V notch.
Calculation
2 = Ratiometric.
No. of Alarms
0 = No Alarms
Xducer
1 = dB3
Volume Units
6 = Mil USG
Time Units
4 = Per Day
Measnt. Units
5 = inches
Empty Level
40.0 inches
Minimum Head
0.000 inches
Maximum Head
15.0 inches
Total Enable
1 = On
Totaliser ( R )
0 = No
Total Multiplier
7 = 1000
Maximum Flow
2.2
Programming is now complete and the unit can now be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the
FlowCERT
LITE
will return to
Run Mode
.